460 Volt Q4 Series
Read these instructions thoroughly before starting the installation. Follow
all precautions and warnings contained within these instructions and on
the unit.
These instructions are primarily intended to assist qualified individuals
experienced in the proper installation of heating and/or air conditioning
appliances. Some local codes require licensed installation/service per-
sonnel for this type equipment. All installations must be in accordance
with these instructions and with all applicable national and local codes
and standards.
Installation Instructions
Single Package Heat Pump
IMPORTANT
Vue de la page 0
1 2 3 4 5 6 ... 18 19

Résumé du contenu

Page 1 - Installation Instructions

460 Volt Q4 SeriesRead these instructions thoroughly before starting the installation. Followall precautions and warnings contained within these inst

Page 2 - TABLE OF CONTENTS

10interval settings are available: 30 minutes, 60minutes, and 90 minutes. Time setting selectionis dependent on the climate where the unit isbeing in

Page 3 - SECTION 1. OWNER INFORMATION

11UNIT MAINTENANCE! WARNING:To avoid risk of electrical shock, personalinjury, or death, disconnect all electricalpower to the unit before performing

Page 4 - SPECIFICATIONS

12Typical Wiring (Field Supplied)for 1-Stage Cool, 1-Stage HeatTypical Wiring (Field Supplied)for 2-Stage Cool, 1-Stage HeatFigure 10. Typical Thermos

Page 5

13Heat Pump in Heating* Note: All pressures are listed inpsig. and all temperatures in deg. F.— Shaded Boxes indicate flooded conditions— Rated Design

Page 6 - Side View Back View

14Table 2a. Q4SA Heating Charging ChartsHeat Pump in Heating* Note: All pressures are listed inpsig. and all temperatures in deg. F.— Shaded Boxes ind

Page 7

15Q4SA-036OUTDOOR TEMPERATURE ( °F )70 75 80 85 90 95 100 105Suct. Pres.Disch. Pres.Disch. Temp.Disch. Pres.Disch. Temp.Disch. Pres.Disch. Temp.Disch.

Page 8

16Q4SA-060OUTDOOR TEMPERATURE ( °F )70 75 80 85 90 95 100 105Suct. Pres.Disch. Pres.Disch. Temp.Disch. Pres.Disch. Temp.Disch. Pres.Disch. Temp.Disch.

Page 9

17Q4 ACCESSORIESDescription Part NumberRoof Curb (8") 547830Roof Curb (14") 547831Manual Fresh Air Damper 547832Economizer, downflow 547833S

Page 10 - WARNING:

18Convertible Packaged Heat Pump 460 Volt Three Phase 60HzNNOTES:1. Disconnect all power before servicing.2. For supply connections use copper cond

Page 11 - CAUTION:

INSTALLER:PLEASE LEAVE THESEINSTALLATION INSTRUCTIONSWITH THE HOMEOWNER.R®ASCOMPLYIITNGWHTTHNISUIHASBIDDARISTANAR210TAIDNFIEDTRECEENR-COIIONINGTAIDNR-

Page 12 - - Speed set at factory

2TABLE OF CONTENTSOWNER INFORMATION ... 3SPECIF

Page 13 - Heat Pump in Heating

3It is the sole responsibility of the homeowner tomake certain that heat pump has been correctlyset up and adjusted to operate properly.NORDYNE warran

Page 14

4OPERATING INSTRUCTIONSTo Operate Your Heat Pump For Cooling —1. Set the thermostat system switch to COOLand the thermostat fan switch to AUTO. (See

Page 15 - Heat Pump in Cooling

5All models are shipped from the factory with thefollowing:1. Zero clearance to combustibles2. Multi-speed direct-drive blower.3. Blower Speed Relay.4

Page 16

6Figure 3. Dimensions24.913.516.023.512.013.313.516.012.0CGA47.53/4" NPT FemaleDrain ConnectorBSUPPLYRETURNTop ViewSide View Back ViewCenter of

Page 17 - Q4 ACCESSORIES

7Figure 4. Minimum Clearances36"36"6"72"36"Condensate DrainFigure 5. Condensate DrainUNIT INSTALLATIONGround Level — When in

Page 18

8Acoustical Duct Work — Certain installationsmay require the use of acoustical lining insidethe supply duct work. Acoustical insulation mustbe in acc

Page 19 - ¢707885W¤

9Use a separate branch electrical circuit for thisunit. A means of electrical disconnect must belocated within sight of and readily accessibilityto t